Toronto address · Ward 5, York South-Weston
170 Emmett Ave
The City of Toronto has 29 building permits since 2017 (18 still open) on record for this address.
Building permits
Every permit the City lists for this address since 2017, and any still open from before, newest first.
- Cancelled
Conditional permit · Partial permit - structural framing
Conditional Permit - Part Permit - Rev - Revisions to the previously issued Building Permit 19 232674 BLD 00 NB for the following areas: loading dock, West Lawn, (addition of) north east parking lot.Proposal to construct a new 6 storey facility/ healthcare centre with mechanical penthouse and 3 levels of underground for West Park Healthcare Centre.
Applied Oct 31, 2025 · completed Jan 22, 2026 · Permit 19 232674 STR (revision 01)
- Revision issued
Heating and ventilation
Revision 01 - see cover letter a. Inline exhaust fan IF-1 used for type2/class 2 heat exhaust relocated. b. Exhaust duct to IF-1 and branch ducts from exhaust grilles modified. c. Revised ductwork from IF-1 to base building general exhaust duct. d. Provide inline carbon filter for IF-1. e. Provide fire dampers in 2h rated vestibule wall for fresh air intake duct to FCU-2. 2. DRAWING M9.0 a. Added specification for carbon filter for exhaust fan IF-1.HVAC - Proposed interior alteration for new "Freshii / Second Cup" kiosk in Food Court
Applied Jul 15, 2025 · issued Jul 22, 2025 · Permit 24 239384 HVA (revision 01)
- Approved
Alternative solution
Proposal for Alternative Solutions for exterior wall fire rating
Applied Mar 18, 2025 · completed May 1, 2025 · Permit 25 130836 ALT
- Closed
Fire and security upgrade
FS - Sprinkler Shop Drawing - Proposed interior alteration for new "Freshii / Second Cup" kiosk in Food Court
Applied Jan 2, 2025 · issued Jun 2, 2025 · completed Jun 2, 2025 · Permit 24 239384 FSU
- Revision issued
Heating and ventilation
HVAC - Rev - Revisions to the previously issued Building Permit 19 232674 BLD 00 NB for the following areas: loading dock, West Lawn, (addition of) north east parking lot.Proposal to construct a new 6 storey facility/ healthcare centre with mechanical penthouse and 3 levels of underground for West Park Healthcare Centre.
Applied Nov 15, 2024 · issued Jan 10, 2025 · Permit 19 232674 HVA (revision 01)
- Inspections under way
Heating and ventilation
HVAC - Proposed interior alteration for new "Freshii / Second Cup" kiosk in Food Court
Applied Nov 15, 2024 · issued Jan 2, 2025 · Permit 24 239384 HVA
- Closed
Plumbing
Plumbing - Proposed interior alteration for new "Freshii / Second Cup" kiosk in Food Court
Applied Nov 15, 2024 · issued Jan 2, 2025 · completed Jul 30, 2025 · Permit 24 239384 PLB
- Revision issued
Plumbing
Plumbing - Rev- Revisions to the previously issued Building Permit 19 232674 BLD 00 NB for the following areas: loading dock, West Lawn, (addition of) north east parking lot.Proposal to construct a new 6 storey facility/ healthcare centre with mechanical penthouse and 3 levels of underground for West Park Healthcare Centre.
Applied Nov 15, 2024 · issued Jan 10, 2025 · Permit 19 232674 PLB (revision 01)
- Inspections under way
Addition or alteration · Interior alterations
Proposed interior alteration for new "Freshii / Second Cup" kiosk in Food Court
Applied Nov 15, 2024 · issued Jan 2, 2025 · Permit 24 239384 BLD
- Examiner's notice sent
New building
Rev - Revisions to the previously issued Building Permit 19 232674 BLD 00 NB for the following areas: loading dock, West Lawn, (addition of) north east parking lot.Proposal to construct a new 6 storey facility/ healthcare centre with mechanical penthouse and 3 levels of underground for West Park Healthcare Centre.
Applied Nov 12, 2024 · Permit 19 232674 BLD (revision 01)
- Closed
Plumbing
Plumbing - Proposed retail pharmacy (no compounding), empty unit fit-up
Applied Jun 13, 2024 · issued Jul 2, 2024 · completed Aug 25, 2024 · Permit 24 145159 PLB
- Closed
Heating and ventilation
HVAC - Proposed retail pharmacy (no compounding), empty unit fit-up
Applied May 7, 2024 · issued Jun 6, 2024 · completed Aug 25, 2024 · Permit 24 145159 HVA
Show 17 more permits
- Closed
Addition or alteration · Interior alterations
Proposed retail pharmacy (no compounding), empty unit fit-up
Applied May 7, 2024 · issued Jun 5, 2024 · completed Sep 17, 2024 · Permit 24 145159 BLD
- Closed
Demolition
Demolish rehab building (Gage) of West Park Healthcare Centre in order to construct the North Parking Lot to the new hospital facility (related building permit: 19 232674 BLD 00 NB)
Applied Dec 1, 2022 · issued May 17, 2023 · completed Jul 10, 2025 · Permit 22 235082 DEM
- Inspections under way
Demolition
Demolish Main Building of West Park Healthcare Centre in order to construct the West Lawn to the new hospital facility (related building permit: 19 232674 BLD 00 NB)
Applied Dec 1, 2022 · issued May 17, 2023 · Permit 22 235120 DEM
- Closed
Demolition
Demolish the power plant of West Park Healthcare Centre in order to construct the West Lawn to the new hospital facility (related building permit: 19 232674 BLD 00 NB)
Applied Dec 1, 2022 · issued May 17, 2023 · completed Jul 10, 2025 · Permit 22 235162 DEM
- Closed
Demolition
Demolish the office building (Ruddy) of West Park Healthcare Centre in order to construct the West Lawn to the new hospital facility (related building permit: 19 232674 BLD 00 NB)
Applied Dec 1, 2022 · issued May 17, 2023 · completed Jul 10, 2025 · Permit 22 235147 DEM
- Refused
Alternative solution
The proposed alternative solution relates the existing duct penetration to the familiar solution of a pipe penetrating a fire resistance rated partition with a ULC listed firestop assembly as required by OBC 3.1.9. This solution provides a similar rating to a noncombustible drainage or HVAC pipe passing through a rated partition.
Applied Jul 6, 2022 · completed Aug 15, 2022 · Permit 22 172909 ALT
- Approved
Alternative solution
Proposal for an alternative solution to address the use of electromagnetic locking devices on the exit stair doors in the West Park Health Care Centre
Applied Jun 3, 2022 · completed Jul 20, 2022 · Permit 22 156491 ALT
- Closed
Conditional permit · New building
Conditional Permit - Proposal to construct a new 6 storey facility/ healthcare centre with mechanical penthouse and 3 levels of underground for West Park Healthcare Centre.
Applied Mar 31, 2021 · issued Nov 25, 2021 · completed Feb 23, 2024 · Permit 19 232674 BLD
- Approved
Alternative solution
This alternative solution addresses the travel distance to an exit in the southwest corner of the p2 and p3 parking levels, with a maximum travel distance to exit stair a measured as 47.90 m. The alternative solution report compares the egress performance level of the current design with an occupant load on each parking level of 111 persons as per obc table 3.1.17.1 with maximum travel distance of 47.90 m, versus an obc acceptable design scenario of 360 persons based on the available exit capacity with a maximum travel distance of 45 m.Please refer to report by vortex fire "vft17156 wphc time…
Applied Mar 2, 2021 · completed Apr 13, 2021 · Permit 21 122125 ALT
- Approved
Alternative solution
This alternative solution addresses the proposal to provide soap dispensers in lieu of required recessed soap holders in barrier free showers in the building as required by OBC 3.8.3.13.(2)(i).As part of housekeeping and IPAC(infection prevention and control) practices, bar soaps are not used in the hospital. Soap dispensers will be provided in the barrier free shower rooms for use by occupants in the building.Please refer to report by vortex fire "vft17156 wphc soap holder alt solution 26feb2021" for details of proposal.
Applied Mar 2, 2021 · completed Apr 13, 2021 · Permit 21 122128 ALT
- Approved
Alternative solution
The proposed development consists of six above grade storeys and three below grade storeys. The major occupancy of the building is group B, division 2, care and treatment occupancy with subsidiary groups a, division 2, assembly, group D, business and personal services and group F, division 3, medium hazard industrial occupancies. It is proposed to install shower controls located in barrier free shower areas on the sidewall and not on the wall opposite the entrance to the shower area and that contains the L-shaped grab bar as required by OBC 3.8.3.13.(2)(f) to (h). The barrier free showers are…
Applied Dec 14, 2020 · completed Jan 11, 2021 · Permit 20 228716 ALT
- Approved
Alternative solution
Alternative solution:It is proposed to provide a non-slip shower chair with full back support instead of a fixed or non-spring-loaded hinged seat as required by OBC Div. B 3.8.3.13(2)(e).
Applied May 13, 2020 · completed Sep 14, 2020 · Permit 20 144852 ALT
- Approved
Alternative solution
Alternative solution:it is proposed to not provide back support for water closets in barrier free washrooms in the abibs department (department 12) and tb section 35 room of the proposed building. please refer to report by vortex fire "vft17156r05 wphc abibs dept. and tb alt. solution 05may2020" for details of proposal.
Applied May 13, 2020 · completed Sep 22, 2020 · Permit 20 144857 ALT
- Approved
Alternative solution
Alternative solution:West park health care centre will be provided with a standpipe system, with 65 mm hose connections located within the exit stairs, and on the floor areas where required 33 m hose coverage cannot be achieved with hose connections in the stairs.hose stations will not be provided in the floor areas.
Applied May 13, 2020 · completed Jun 26, 2020 · Permit 20 144841 ALT
- Inspections under way
Drains and site services
Drain - Proposal to construct a new 6 storey facility/ healthcare centre with mechanical penthouse and 3 levels of underground for West Park Healthcare Centre.
Applied Apr 30, 2020 · issued Jun 9, 2020 · Permit 19 232674 DRN
- Inspections under way
Plumbing
Plumbing -Proposal to construct a new 6 storey facility/ healthcare centre with mechanical penthouse and 3 levels of underground for West Park Healthcare Centre.
Applied Oct 7, 2019 · issued Feb 3, 2021 · Permit 19 232674 PLB
- Inspections under way
Heating and ventilation
HVAC - Proposal to construct a new 6 storey facility/ healthcare centre with mechanical penthouse and 3 levels of underground for West Park Healthcare Centre.
Applied Oct 7, 2019 · issued May 11, 2022 · Permit 19 232674 HVA
Committee of Adjustment
No applications to the City's Committee of Adjustment for this address since 2017. That's where an owner asks for a minor variance (a small exception to the zoning by-law) or a consent to divide a lot.
What’s planned nearby
Development sites within 500 m
- Approved
- Under review
Neighbours’ Committee of Adjustment files within 250 m
82 Buttonwood Ave · Minor variance
To alter the development standards as outlined in By-law 1396-2024 to maintain the as-built maintenance garage.
110 m away · filed Mar 18, 2026 · Approved
100 Emmett Ave · Minor variance
To alter a one-storey ancillary structure (portable) by combining two new portables to the existing single portable (fronting onto Emmett Avenue).
230 m away · filed Sep 26, 2017 · Approved
From the City of Toronto’s open data: building permits (active, and cleared since 2017), Committee of Adjustment applications and address points, this record updated Sep 29, 2026, and the development sites from its Development Applications data. Contains information licensed under the Open Government Licence – Toronto. Construction cost estimates and contractors’ names are left out on purpose, and nothing here names an owner.